Cables longer then 6 m are not recommended.
Cable eyes with M6/8 holes should be used.
For supply connection use wires suitable for at least 75°C (167°F).
CAUTION: Replace defective cords or wires immediately.
Connection sequence
Disconnect mains.
Disconnect battery cables from the battery.
Open front cover.
Connect battery cables to the charger. Note that there’s only one
“minus”- Use a fuse according the size of the battery charger.
Connect battery cables to the battery.
Connect the AC-in by means of a 3-core cable of 2.5 – 4 mm²
flexible core to the AC-in terminal block. Note that a real PE-
connection is strictly necessary.
Close the front panel.
Change voltage at appr. 10% of the nominal current
Absorption
Float
12V 24V 12V 24V
LA 14.5 29.0 13.5 27.0
AGM 14.3 28.6 13.3 26.6
GEL 14.2 28.4 13.5 27.0
Other 14.7 29.4 13.7 27.4