USER MANUAL INSTALLATION MANUAL Quattro 12/5000/200 Quattro 24/5000/120 Quattro 48/5000/70 Remark: DIP switch functionality has cha
9 Special indications Set with limited input current charger inverter mains on inverter on on bulk overload off absorption low batte
10 4. Installation This product may only be installed by a qualified electrical engineer. 4.1 Contents of the box The Quattro box contains the fol
11 4.4 Connecting the battery leads In order to use the full potential of the Quattro, batteries of sufficient capacity and battery leads with the c
12 AC-out-1 (see appendix A) The load is connected to these terminals. If AC voltage is available on AC-in-1 or AC-in-2, AC-out-1 will be connected
13 4.6.6 Connecting Quattros in parallel (see appendix C) The Quattro can be connected in parallel with several identical devices. To this end, a co
14 5. Configuration • Settings may only be changed by a qualified electrical engineer. • Read the instructions thoroughly before implementing cha
15 Inverter voltage Output voltage of the Quattro in battery operation. Adjustability: 210 – 245V Stand-alone / parallel operation / 2-3 phase sett
16 Dynamic current limiter Intended for generators, the AC voltage being generated by means of a static inverter (so-called ‘inverter’ generators).
17 5.3 Configuration by computer All settings can be changed by means of a computer or with a VE.Net panel (except for the multi-functional relay an
18 5.5 Configuration with DIP switches A number of settings can be changed using DIP switches (see appendix A, position M). This is done as follo
1 1. SAFETY INSTRUCTIONS In general Please read the documentation supplied with this product first, so that you are familiar with the safety signs e
19 5.5.1.3 Charging current limitation (default setting 75%) For maximum battery life, a charging current of 10% to 20% of the capacity in Ah should
20 DIP switches ds2 and ds1 are reserved for the selection of stand-alone, parallel or 3-phase operation Step 1: Setting ds2 and ds1 for stand-alon
21 Step 1: Setting ds2 and ds1 for parallel operation The current settings (AC current limitation and charging current) are multiplied by the num
22 Step 1: Setting ds2 and ds1 for 3-phase operation As the table above shows, the current limits for each phase should be set separately (ds8
23 5.5.2 Step 2: Other settings The remaining settings are not relevant for slaves. Some of the remaining settings are not relevant for followers (
24 Step 2: Exemplary setting for parallel mode In this example, the master is configured according to factory settings. The slaves do not require se
25 7 Error indications With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your Victro
26 The absorption voltage is set to an incorrect level (too high). Set the absorption voltage to the correct level. The float voltage is set to an i
27 7.3.2 VE.Bus error codes A VE.Bus system can display various error codes. These codes are displayed with the "inverter on", "bulk&
28 8. Technical specifications Quattro 12/5000/200 24/5000/120 48/5000/70 PowerControl
2 2. DESCRIPTION 2.1 In general The basis of the Quattro is an extremely powerful sine inverter, battery charger and automatic switch in a compact c
29 APPENDIX A: Connection overview
30 APPENDIX A: Connection overview English: Dutch: A AC input (generator input) AC-in-1. Left to ri
31 APPENDIX B: Block diagram
32 APPENDIX C: Parallel connection
33 APPENDIX D: Three-phase connection
34 APPENDIX E: Charge characteristics C h a rg e c u rre n t0%2 0 %4 0 %6 0 %8 0 %1 0 0 %1 2 0 %T im eA m p sC h ar g e v o lta g e1 01 11 21 31
35 APPENDIX F: Temperature compensation 10.010.511.011.512.012.513.013.514.014.515.00 5 10 15 20 25 30 35 40 45 50 55 60Battery temperatureVolt
36 APPENDIX G: Dimensions
37 Serial number: Distributor: Victron Energy B.V. The Netherlands Phone:+31 (0)36 535 97 00 Fax: +31 (0)36 535 97 40 E-mail:sales@victronenergy
3 2.2 Battery charger Adaptive 4-stage charging characteristics: bulk – absorption – float – storage The microprocessor-driven adaptive battery man
4 3. Operation 3.1 “On / stand by / charger only” switch When the switch is switched to “on”, full device operation is initiated. The inverter will
5 3.4 LED indications and their meaning LED off LED flashes LED lights Inverter charger inverter mains on inverter on on bulk over
6 off absorption low battery float charger only temperature charger inverter mains on inverter on on bulk overload off absorp
7 charger inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature – If the L
8 charger inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature The AC volt