Telecom batteries
www.victronenergy.com
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: sales@victronenergy.com | www.victronenergy.com
12V AGM Telecom battery 115Ah 165Ah 200Ah
Capacity 1 / 3 / 5 / 10 / 20 hours
(% of nominal)
60 / 75 / 82 / 91 / 100 (@ 70ºF/25ºC, end of discharge 10,5V)
Capacity 10 / 20 / 30 / 40 minutes
(% of nominal)
33 / 44 / 53 / 57 (@ 70ºF/25ºC, end of discharge 9,6V)
Nominal capacity (77ºF/25ºC, 10,5V) 115Ah 165Ah 200Ah
Cold Cranking Amps @ 0ºF/-18ºC 1000 1500 1800
DIN cold start current (A) @ 0ºF/-18ºC 600 900 1000
Short Circuit Current (A) 3500 5000 6000
Reserve Capacity (minutes) 200 320 400
Shelf life @ 70ºF/20ºC 1 year
Absorption voltage (V) @ 70ºF/20ºC 14,4 – 14,7
Float voltage (V) @ 70ºF/20ºC 13,6 – 13,8
Storage voltage (V) @ 70ºF/20ºC 13,2
Float design life @ 70ºF/20ºC 12 years
Cycle design life @ 100% discharge 250
Cycle design life @ 50% discharge 500
Cycle design life @ 30% discharge 1000
Dimensions (lxwxh, mm) 395 x 110 x 293mm 548 x 105 x 316mm 546 x 125 x 323mm
Dimensions (lxwxh, inches) 153.7 x 43.3 x 115.3 215.7 x 41.3 x 124.4 214.9 x 49.2 x 127.1
Weight (kg / pounds) 35kg / 77 lbs 49kg / 88 lbs 60kg / 132 lbs\
Designed for telecom applications; excellent “floor space savers” for marine and vehicle applications
The deep cycle AGM telecom series has been designed for use in telecom systems. With front access terminals
and small footprint, the batteries are ideal for racked systems. Similarly, these batteries can help solve limited
floor space and access problems on board boats and vehicles.
AGM technology
AGM stands for Absorbent Glass Mat. In these batteries the electrolyte is absorbed into a glass-fibre mat
between the plates by capillary action.
Low self-discharge
Because of the use of lead calcium grids and high purity materials, Victron VRLA batteries can be stored during
long periods of time without recharge. The rate of self-discharge is less than 2% per month at 20°C. The self
discharge doubles for every increase in temperature with 10°C.
Low internal resistance
Accepts very high charge and discharge rates
High cyclic life capability
More than 500 cycles at 50 % depth of discharge
Learn more about batteries and battery charging
To learn more about batteries and charging batteries, please refer to our book ‘Energy Unlimited’ (available free
of charge from Victron Energy and downloadable from www.victronenergy.com
).
Telecom batteries
heavy duty, front access
Telecom Battery
Battery AGM 12V 200Ah
Telecom Battery
Battery AGM 12V 200Ah